Google's London outage: a PLC fault told the generators utility power was healthy
Google says a misconfigured PLC never sent a start command to backup generators in its europe-west2-b zone on 20 October, after one utility feeder failed while the other was open for repairs.
Google has explained why backup generators did not start during an October outage in its London cloud region. In an update to its status page, the company said a misconfigured programmable logic controller (PLC) never told the generators to start when utility power was lost to the europe-west2-b zone.
What happened
According to Google, one utility feeder failed because of an external underground cable fault on the utility network outside the data centre. The second feeder had been deliberately opened for repairs, following issues found in a quarterly generator load test on 14 October. With both feeds dead, the site was left relying on batteries and generators.
The battery stage did its job: Google says its static UPS systems provide 5 minutes of autonomous runtime. The generator stage did not. Google says the PLC logic indicated that a healthy utility source was available, so it did not issue a start command to the generator plant. The Register adds that a voltage-sensing design flaw contributed.
What this measures, and what it does not
The five-minute figure is a design runtime for the batteries, not a measured outage duration. It is a bridge to generator start, so any failure of the automatic start path turns a short utility loss into a zone-wide outage. Google's account is its own root-cause analysis; it has not been independently audited, and the fixes it describes are reported as tested by Google.
The case is a reminder that redundancy in hardware (two feeders, UPS, a generator bank) depends on control logic that is often a single point of failure in practice, even when the controller itself is dual-redundant. It also shows how maintenance can quietly remove a layer of redundancy: with one feeder open, the site no longer had the margin its design assumed.
Why it matters
AI and cloud buildout is concentrating more load in fewer facilities, and resilience claims for those sites rest on power-chain behaviour that is rarely tested end to end. A configuration error in a controller, rather than a failed generator, was enough here. Operators and customers who plan around availability zones should treat power-control logic as part of the failure domain.
What to watch
- Whether Google publishes the full set of electrical changes and the testing it says it has done.
- Google's planned improvements to customer alerts for location-impacting incidents and wider platform-level testing of infrastructure events.
- Whether other operators review PLC start logic and maintenance procedures that remove a feeder from service.